A grid-voltage-sensorless resistive active power filter with series LC-filter

Publikation: Bidrag til bog/antologi/rapport/konference proceedingKonferenceartikel i proceedingForskningpeer review

2 Citationer (Scopus)

Abstract

Voltage-sensorless control has been investigated for Voltage Source Inverters (VSIs) for many years due to the reduced system cost and potentially improved system reliability. The VSI based Resistive Active Power Filters (R-APFs) are now widely used to prevent the harmonic resonance in power distribution network, for which the voltage sensors are needed in order to obtain the current reference. In this paper a grid-voltage-sensorless control strategy is proposed for the R-APF with series LC-filter. Unlike the traditional resistance emulation method, this proposed control method re-shapes the output impedance of the R-APF at the harmonic frequencies, which is independent of the current reference. A fundamental grid voltage estimation method is also proposed to control the DC-link voltage. The performance of the proposed control method is verified in both simulations and experiments. The results show good accuracy of the emulated resistance and functionality of the DC-link voltage control. With the proposed method, the cost of the R-APF can also be reduced with potentially improved system reliability.
OriginalsprogEngelsk
TitelProceedings of 2017 IEEE Energy Conversion Congress and Exposition (ECCE)
Antal sider8
ForlagIEEE Press
Publikationsdatookt. 2017
Sider3004-3011
ISBN (Elektronisk)978-1-5090-2998-3
DOI
StatusUdgivet - okt. 2017
Begivenhed2017 IEEE Energy Conversion Congress and Exposition (ECCE) - Cincinnati, Ohio, USA
Varighed: 1 okt. 20175 okt. 2017

Konference

Konference2017 IEEE Energy Conversion Congress and Exposition (ECCE)
Land/OmrådeUSA
ByCincinnati, Ohio
Periode01/10/201705/10/2017

Fingeraftryk

Dyk ned i forskningsemnerne om 'A grid-voltage-sensorless resistive active power filter with series LC-filter'. Sammen danner de et unikt fingeraftryk.

Citationsformater