Analysis of a commercial wind farm in Taiwan : Part I: Measurement results and simulations
Publikation: Forskning - peer review › Tidsskriftartikel
This paper presents both steady-state performance and dynamic simulations of a commercial wind farm (WF) in Taiwan through field measurement results and computer simulations. The companion paper in Part II discusses the dynamic and transient analyzed results of using current-limit reactors (CLRs) and load tap changers on power-quality improvement of the studied WF. With 23 2-MW DFIG-type wind turbine generators, this WF is connected to the 161-kV extra high-voltage substation of Taiwan Power System through a 23/161-kV 60-MVA step-up main transformer from six feeders with CLRs. Through comparing field measured results, this paper establishes a simulation model to simulate and analyze the steady-state and dynamic characteristics of the studied WF which is subject to disturbance conditions under different wind-speed conditions.
| Originalsprog | Engelsk |
|---|---|
| Tidsskrift | I E E E Transactions on Industry Applications |
| Udgivelsesdato | 23 dec 2010 |
| Vol/bind | 47 |
| Tidsskriftsnummer | 2 |
| Sider | 939-953 |
| Antal sider | 15 |
| ISSN | 0093-9994 |
| DOI | |
| Status | Udgivet |
ID: 51817658