Full Scale Earth Fault Experiments on 10 kV laboratory network with comparative Measurements on Conventional CT's and VT's

Stefan Sørensen, Hans Ove Nielsen, Birgitte Bak-Jensen

Publikation: Bidrag til bog/antologi/rapport/konference proceedingKonferenceartikel i proceedingForskning

Abstract

In this paper we present a result of a full scale earth fault carried out on the 10 kV research/laboratory distribution network at Kyndbyvaerket Denmark in May 2001. The network is compensated through a Petersen-Coil and current and voltage measurements were measured on conventional current transformers (CT?s) and voltage transformers (VT?s) by an optical link. Comparison with a similar earlier performed experiment caried out autumn 1998, where current and voltage measurements were measured with high bandwidth Rugowski-coils and high voltage Tektronix probes, gave remarkable results. The necessity of high bandwidth measurement equipment for earth fault measurements on compensated distribution networks can be undermined, since it will be shown that the transient signal transfer through conventional CT?s and VT?s for further signal analysis is sufficient. Caused the inadequacy three phase conductor cable models in PSCDAD/EMTDC v.3, the simulations of the whole laboratory network shows more or less good identity with the measurements.
OriginalsprogEngelsk
Titel2002 IEEE Power Engineering Society Summer Meeting
ForlagSPIE - International Society for Optical Engineering
Publikationsdato2002
Sider7
ISBN (Trykt)0780375181
StatusUdgivet - 2002
BegivenhedFull Scale Earth Fault Experiments on 10 kV laboratory network with comparative Measurements on Conventional CT's and VT's -
Varighed: 19 maj 2010 → …

Konference

KonferenceFull Scale Earth Fault Experiments on 10 kV laboratory network with comparative Measurements on Conventional CT's and VT's
Periode19/05/2010 → …

Bibliografisk note

ISSN ; -

Emneord

  • Petersen-Coil compensation
  • 10 kV laboratory network
  • PSCDAD/EMTDC
  • Earth faults