Optimal Power Consumption in a Central Heating System with Geothermal Heat Pump

Fatemeh Tahersima, Jakob Stoustrup, Henrik Rasmussen

Publikation: Bidrag til tidsskriftKonferenceartikel i tidsskriftForskningpeer review

11 Citationer (Scopus)
1319 Downloads (Pure)

Abstract

Driving a ground source heat pump in a central heating system with the minimum power consumption is studied. The idea of control is based on the fact that, in a heat pump, the temperature of the forward water has a strong positive correlation with the consumed electric power by the compressor. Thus, lowering the temperature of forward water alleviates energy consumption. The hypothesis is that the minimum water temperature is achieved when at least one of the hydronic heaters in the building works at full capacity. The setpoint of the forward water temperature is found by solving a model based optimization problem in a receding finite horizon. The optimization objective is to maintain the local control signal of the largest thermal load near full capacity. The overall control system hierarchy is composed of local PI controllers for each subsystem and an MPC controller which orchestrates the PI controllers. Simulation results for a case study with simplified subsystems' models show considerable energy savings compared to the traditional control scheme for the heat pump.
OriginalsprogEngelsk
BogserieProceedings of the 18th IFAC World Congress, 2011
ISSN1474-6670
StatusUdgivet - 2011
BegivenhedThe 18th World Congress of the International Federation of Automatic Control (IFAC 2011) - Milano, Italien
Varighed: 28 aug. 20112 sep. 2011

Konference

KonferenceThe 18th World Congress of the International Federation of Automatic Control (IFAC 2011)
Land/OmrådeItalien
ByMilano
Periode28/08/201102/09/2011

Fingeraftryk

Dyk ned i forskningsemnerne om 'Optimal Power Consumption in a Central Heating System with Geothermal Heat Pump'. Sammen danner de et unikt fingeraftryk.

Citationsformater