Design of protective inductors for HVDC transmission line within DC grid offshore wind farms

Fujin Deng, Zhe Chen

Research output: Contribution to journalJournal articleResearchpeer-review

73 Citations (Scopus)

Abstract

This paper presents fault analysis and protective inductors design for an offshore wind farm, where the power collection system in the wind farm and the power transmission link to the grid adopt high-voltage direct-current (HVDC) technology. This paper focuses on dealing with short-circuit faults in the HVDC link between the offshore station and the onshore station. The transient characteristics of the transmission system are analyzed in detail. The criteria of selecting protective inductors are proposed to effectively limit the short-circuit current and avoid the damage to the converters. A dc grid offshore wind farm is simulated, and the results demonstrate the effectiveness of the proposed protective inductors design.
Original languageEnglish
JournalI E E E Transactions on Power Delivery
Volume28
Issue number1
Pages (from-to)75-83
Number of pages9
ISSN0885-8977
DOIs
Publication statusPublished - 2013

Keywords

  • DC fault
  • HVDC
  • Offshore wind farms
  • Wind power generation