Harmonic Domain Modelling of Transformer Core Nonlinearities Using the DIgSILENT PowerFactory Software

Claus Leth Bak, Birgitte Bak-Jensen, Wojciech Wiechowski

Research output: Contribution to journalJournal articleResearchpeer-review

2857 Downloads (Pure)

Abstract

This paper demonstrates the results of implementation and verification of an already existing algorithm that allows for calculating saturation characteristics of singlephase power transformers. The algorithm was described for the first time in 1993. Now this algorithm has been implemented using the DIgSILENT Programming Language (DPL) as an external script in the harmonic domain calculations of a power system analysis tool PowerFactory [10]. The algorithm is verified by harmonic measurements on a single-phase power transformer. A theoretical analysis of the core nonlinearities phenomena in single and three-phase transformers is also presented. This analysis leads to the conclusion that the method can be applied for modelling nonlinearities of three-phase autotransformers.
Original languageEnglish
JournalJakosc i Uzytkowanie Energii Elektrycznej
VolumeXIV
Issue number1
Pages (from-to)3-11
Number of pages9
ISSN1234-6799
Publication statusPublished - 2008

Keywords

  • Autotransformers
  • Harmonic analysis
  • Nonlinearities
  • Simulation software
  • Transformer cores

Fingerprint

Dive into the research topics of 'Harmonic Domain Modelling of Transformer Core Nonlinearities Using the DIgSILENT PowerFactory Software'. Together they form a unique fingerprint.

Cite this