TY - JOUR
T1 - An Islanding Microgrid Power Sharing Approach Using Enhanced Virtual Impedance Control Scheme
AU - He, Jinwei
AU - Li, Yun Wei
AU - Guerrero, Josep M.
AU - Blaabjerg, Frede
AU - Vasquez, Juan Carlos
PY - 2013/11
Y1 - 2013/11
N2 - In order to address the load sharing problem in islanding microgrids, this paper proposes an enhanced distributed generation (DG) unit virtual impedance control approach. The proposed method can realize accurate regulation of DG unit equivalent impedance at both fundamental and selected harmonic frequencies. In contrast to conventional virtual impedance control methods, where only a line current feed-forward term is added to the DG voltage reference, the proposed virtual impedance at fundamental and harmonic frequencies is regulated using DG line current and point of common coupling (PCC) voltage feed-forward terms, respectively. With this modification, the impacts of mismatched physical feeder impedances are compensated. Thus, better reactive and harmonic power sharing can be realized. Additionally, this paper also demonstrates that PCC harmonic voltages can be mitigated by reducing the magnitude of DG unit equivalent harmonic impedance. Finally, in order to alleviate the computing load at DG unit local controller, this paper further exploits the band-pass capability of conventionally resonant controllers. With the implementation of proposed resonant controller, accurate power sharing and PCC harmonic voltage compensation are achieved without using any fundamental and harmonic components extractions. Experimental results from a scaled single-phase microgrid prototype are provided to validate the feasibility of the proposed virtual impedance control approach.
AB - In order to address the load sharing problem in islanding microgrids, this paper proposes an enhanced distributed generation (DG) unit virtual impedance control approach. The proposed method can realize accurate regulation of DG unit equivalent impedance at both fundamental and selected harmonic frequencies. In contrast to conventional virtual impedance control methods, where only a line current feed-forward term is added to the DG voltage reference, the proposed virtual impedance at fundamental and harmonic frequencies is regulated using DG line current and point of common coupling (PCC) voltage feed-forward terms, respectively. With this modification, the impacts of mismatched physical feeder impedances are compensated. Thus, better reactive and harmonic power sharing can be realized. Additionally, this paper also demonstrates that PCC harmonic voltages can be mitigated by reducing the magnitude of DG unit equivalent harmonic impedance. Finally, in order to alleviate the computing load at DG unit local controller, this paper further exploits the band-pass capability of conventionally resonant controllers. With the implementation of proposed resonant controller, accurate power sharing and PCC harmonic voltage compensation are achieved without using any fundamental and harmonic components extractions. Experimental results from a scaled single-phase microgrid prototype are provided to validate the feasibility of the proposed virtual impedance control approach.
U2 - 10.1109/TPEL.2013.2243757
DO - 10.1109/TPEL.2013.2243757
M3 - Journal article
SN - 0885-8993
VL - 28
SP - 5272
EP - 5282
JO - IEEE Transactions on Power Electronics
JF - IEEE Transactions on Power Electronics
IS - 11
ER -