Separation of Wear-Out Failure Modes of IGBT Modules in Grid-Connected Inverter Systems

Uimin Choi, Frede Blaabjerg

Research output: Contribution to journalJournal articleResearchpeer-review

55 Citations (Scopus)

Abstract

Wear-out condition monitoring of IGBT modules with failure mode separation gives some benefits. First, it allows proactive maintenance plans. Further, depending on the failure mode, different proactive control strategies can be applied to inverters in order to improve the reliability and availability of power electronic systems. This paper proposes a new method for the separation of two representative wear-out failure modes of wire-bonded IGBT modules in a grid-connected inverter in real time. The proposed method requires just two preliminary I- V characterizations of IGBT modules. Further, only one monitoring parameter is used, and thus, it is cost-effective compared with using one more monitoring parameter in order to separate failure modes. Experimental results verify the validity and feasibility of the proposed method.
Original languageEnglish
JournalI E E E Transactions on Power Electronics
Volume33
Issue number7
Pages (from-to)6217 - 6223
Number of pages7
ISSN0885-8993
DOIs
Publication statusPublished - Jul 2018

Keywords

  • Condition monitoring
  • Inverter
  • IGBT module
  • Reliability
  • Wear-out failure

Fingerprint

Dive into the research topics of 'Separation of Wear-Out Failure Modes of IGBT Modules in Grid-Connected Inverter Systems'. Together they form a unique fingerprint.

Cite this