Single-phase AutoReClosure ARC failure on 400 kV combinedcable/overhead line with permanently connected shunt reactor

Claus Leth Bak, Kim Søgaard

Research output: Contribution to book/anthology/report/conference proceedingArticle in proceedingResearchpeer-review

239 Downloads (Pure)

Abstract

This paper demonstrates the results from a detailed study of the dynamic behavior of a shunt reactor compensated 400 kV combined cable/overhead line. This is accomplished by means of theoretical considerations, simulations and measurements. The work presented here is based on a real-life operating 400 kV power system and initiated by Danish TSO Energinet.dk after having measured the voltage of the cable/overhead line after disconnection. A particular decaying dynamic phase voltage containing voltages higher than the voltage before disconnection appeared. A simulation model for the entire system consisting of overhead lines, crossbonded cable sections and shunt reactor has been created in PSCAD/EMTDC and verified against measurements with good results. Main focus has been put on the likelihood of having a successful single-phase autoreclosure ARC in such a combined cable/OHL line.
Original languageEnglish
Title of host publicationProceedings of the 8th WSEAS International Conference on Electric Power Systems, High Voltages, Electric Machines (POWER '08) : Recent advances in electric power systems, high voltages, electrical machines
Number of pages10
PublisherWSEAS Press
Publication date2008
Pages118-127
ISBN (Print)978-960-474-026-0
Publication statusPublished - 2008
EventRecent advances in electric power systems, high voltages, electrical machines WSEAS POWER08 - Venedig, Italy
Duration: 21 Nov 200823 Nov 2008
Conference number: 8

Conference

ConferenceRecent advances in electric power systems, high voltages, electrical machines WSEAS POWER08
Number8
Country/TerritoryItaly
CityVenedig
Period21/11/200823/11/2008

Keywords

  • 400 kV cable
  • Single-phase autoreclosure,
  • Shunt reactor
  • Resonance
  • Mutual coupling