Switching overvoltage when disconnecting a combined 400 kVcable/overhead line with permanently connected shunt reactor

Claus Leth Bak, Kim Søgaard

Research output: Contribution to journalJournal articleResearchpeer-review

2592 Downloads (Pure)

Abstract

This paper demonstrates the results from a detailed study of the dynamic behavior of a shunt reactor compensated 400 kV combined cable/overhead line. This is accomplished by means of theoretical considerations, simulations and measurements. The work presented here is based on a real-life operating 400 kV power system and initiated by Danish TSO Energinet.dk after having measured the voltage of the cable/overhead line after disconnection. A particular decaying dynamic phase voltage containing voltages higher than the voltage before disconnection appeared. A simulation model for the entire system consisting of overhead lines, crossbonded cable sections and shunt reactor has been created in PSCAD/EMTDC and verified against measurements with good results. Main focus has been put on the generation of switching overvoltages. It is shown that the generation of switching overvoltages is caused by slightly different resonant frequencies of the three phases which are reflected between the phases by mutual couplings in such a way that a low-frequent modulation appears in the phase voltages.
Original languageEnglish
JournalWSEAS Transactions on Electronics
Number of pages10
ISSN1109-9445
Publication statusPublished - 2008

Keywords

  • 400 kV cable
  • Disconnection
  • Switching overvoltage
  • Resonance
  • Mutual coupling
  • Shunt reactor
  • Low frequent modulation

Fingerprint

Dive into the research topics of 'Switching overvoltage when disconnecting a combined 400 kVcable/overhead line with permanently connected shunt reactor'. Together they form a unique fingerprint.

Cite this