Switching Overvoltages in 60 kV reactor compensated cable grid due to resonance after disconnection

Claus Leth Bak, Haukur Baldursson, Abdoul M. Oumarou

Research output: Contribution to book/anthology/report/conference proceedingArticle in proceedingResearchpeer-review

301 Downloads (Pure)

Abstract

Some electrical distribution companies are nowadays replacing overhead lines with underground cables. These changes from overhead to underground cable provoke an increased reactive power production in the grid. To save circuit breakers the reactors needed for compensating this excessive reactive power could be directly connected to long cables. Switching both cable and reactor together will cause resonance to occur between the cable capacitance and the inductance of the cable during last end disconnection. Similar type of resonance condition is known to have caused switching overvoltages on the 400kV grid in Denmark. Therefore it is considered necessary to analyze further whether connecting a reactor directly to 60kV cable can cause switching overvoltages. A model in PSCAD was used to analyze which parameters can cause overvoltage. The switching resonance overvoltage was found to be caused by strong mutual couplings between the phases along with different resonance frequencies in the phases caused by unbalance in the grid. This is though not found to cause damaging overvoltages in a cable grid as in ENV-net's grid with the expected reactor values.
Original languageEnglish
Title of host publicationProceedings of the 8th WSEAS International Conference on Electric Power Systems, High Voltages, Electric Machines (POWER '08) : Recent advances in electric power systems, high voltages, electrical machines
Number of pages9
PublisherWSEAS Press
Publication date2008
Pages109-117
ISBN (Print)978-960-474-026-0
Publication statusPublished - 2008
Event2008 WSEAS International Conferences - Venedig, Italy
Duration: 21 Nov 200823 Nov 2008

Conference

Conference2008 WSEAS International Conferences
Country/TerritoryItaly
CityVenedig
Period21/11/200823/11/2008

Keywords

  • Switching Transients
  • Underground Cables
  • Shunt reactors
  • Resonance

Fingerprint

Dive into the research topics of 'Switching Overvoltages in 60 kV reactor compensated cable grid due to resonance after disconnection'. Together they form a unique fingerprint.

Cite this