Utilisation of symmetrical components in a communication-based protection for loop MV feeders with variable short-circuit power

Research output: Contribution to journalConference article in JournalResearchpeer-review

Abstract

Variability of the available short-circuit power also implies variation of the fault level, which can potentially cause several protection problems in the electric networks. In this paper, a novel protection method that is insensitive to the fault level changes caused by variable short-circuit power is presented. It relies on utilisation of symmetrical components of the short-circuit currents and on communication between the protection relays. The proposed method addresses the Single Phase to Ground (SPG) faults occurring in directly grounded distribution networks, with focus on closed-loop Medium Voltage (MV) feeders. Case studies are presented, which demonstrate that the proposed protection scheme is capable of effectively detecting the SPG faults in closed-loop feeders with variable short-circuit power.
Close

Details

Variability of the available short-circuit power also implies variation of the fault level, which can potentially cause several protection problems in the electric networks. In this paper, a novel protection method that is insensitive to the fault level changes caused by variable short-circuit power is presented. It relies on utilisation of symmetrical components of the short-circuit currents and on communication between the protection relays. The proposed method addresses the Single Phase to Ground (SPG) faults occurring in directly grounded distribution networks, with focus on closed-loop Medium Voltage (MV) feeders. Case studies are presented, which demonstrate that the proposed protection scheme is capable of effectively detecting the SPG faults in closed-loop feeders with variable short-circuit power.
Original languageEnglish
JournalThe Journal of Engineering
Pages (from-to)1-7
Number of pages7
ISSN2051-3305
DOI
StateE-pub ahead of print - 19 Jul 2018
Publication categoryResearch
Peer-reviewedYes
EventThe 14th International Conference on Developments in Power System Protection - The Europa Hotel, Belfast, United Kingdom
Duration: 12 Mar 201815 Mar 2018
Conference number: 14

Conference

ConferenceThe 14th International Conference on Developments in Power System Protection
Number14
LocationThe Europa Hotel
CountryUnited Kingdom
CityBelfast
Period12/03/201815/03/2018

    Research areas

  • Symmetrical components, Communication-based protection, Phase to ground fault, Loop feeder, Variable fault currents

Map