This paper reports on a comparative study of the indoor environment in two adjacent classrooms, one renovated, and the other non-renovated. The aim of the study was to investigate the positive consequences of renovating classrooms, but also to disclose unanticipated side-effects. The non-renovated classroom was without mechanical ventilation, fitted with woodwool ceiling plates for acoustics and lighting fixtures with horizontal illuminances of 200-300 lux on the tables. The renovated classroom was retrofitted with a new acoustic ceiling made from perforated gypsum tiles and suspended lighting fixtures and mechanical ventilation via decentral room unit mounted below the ceiling. The ventilation air was supplied in the void above the acoustic ceiling, which distributes air through perforations and joints in the ceiling to the occupied zone – a concept often referred to as diffuse ventilation. In this setup, the acoustic ceiling also acted as silencer for the ventilation inlet. Different indoor environmental parameters were comparatively measured in each classroom, including longterm CO2-concentration, temperature and noise levels as well as reverberation time and technical noise from the ventilation quipment. In all respects, the objective measurements improved in the renovated lassroom.
Interviews with pupils and questionnaire surveys were conducted, and – while showing less evidence of the improvements than expected – did indicate increased user satisfaction with the retrofit.
OriginalsprogEngelsk
TitelRoomvent&Ventilation 2018 proceedings : Excellent Indoor Climate and High Performing Ventilation
RedaktørerRisto Kosonen, Mervi Ahola, Jarkko Narvanne
ForlagSIY Indoor Air Information Oy
Publikationsdatojun. 2018
Sider277-282
ISBN (Elektronisk)978-952-5236-48-4
StatusUdgivet - jun. 2018
BegivenhedRoomvent 2018: International Conference on Air Distribution in Rooms - Aalto University, ,Finland, Espoo, Finland
Varighed: 2 jun. 20185 jun. 2018
https://roomventilation2018.org/

Konference

KonferenceRoomvent 2018
LokationAalto University, ,Finland
LandFinland
ByEspoo
Periode02/06/201805/06/2018
Internetadresse

Fingeraftryk Dyk ned i forskningsemnerne om 'A Comparative Study of the Indoor Environmental Quality in Renovated and Non-Renovated Classrooms'. Sammen danner de et unikt fingeraftryk.

Citationsformater