Air tightness measurements in older Danish single-family houses

Lone Hedegaard Mortensen, Niels Christian Bergsøe

Publikation: Bidrag til tidsskriftKonferenceartikel i tidsskriftForskningpeer review

3 Citationer (Scopus)
277 Downloads (Pure)

Resumé

This paper reports and discusses the air tightness of the building envelope in existing single-family houses in Denmark. The air tightness of the building envelope depends in particular on the performance of specific construction details. There is a lack of knowledge about the air tightness of the building envelope of older buildings despite the fact that the air tightness has a major influence on the energy use. In connection with renovation of the Danish building stock, the coming years will see increased focus on the air tightness of the building envelope like in other countries.
This paper presents the results of measurements in 16 single-family houses built between 1880 and 2007. The air tightness of the building envelope was measured according to EN ISO 9972 using the blower-door technique. The results are compared with measurement results of the average air-change rate in the same houses measured over a period of 1-3 weeks when the houses were in normal use.
The measurement results of the air tightness of the building envelope range from 1.1 to 5.8 l/(s·m²) at 50 Pa. The investigated houses are all naturally ventilated. The results of the ventilation measurements showed an outdoor air supply ranging from 0.09 to 0.28 l/(s·m²) per heated floor area, which is below the requirement stipulated in the Danish Building Regulations of 0.3 l/(s·m²).
Typically, leaks are observed in connection with penetrations of the envelope, e.g. for electrical installations, exhaust ducts and chimneys. In addition, leaks are observed around older windows and doors and in connection with wooden ceilings and attic hatches. The findings should be taken into account when renovating older single-family houses.
OriginalsprogEngelsk
TidsskriftEnergy Procedia
Vol/bind132
Sider (fra-til)825-830
Antal sider6
ISSN1876-6102
DOI
StatusUdgivet - 25 okt. 2017
Begivenhed11th Nordic Symposium on Building Physics - The Electro Building at Gløshaugen campus, NTNU, Trondheim, Norge
Varighed: 11 jun. 201714 jun. 2017
Konferencens nummer: 11
http://www.ntnu.edu/web/nsb2017/home
http://www.ntnu.edu/nsb2017

Konference

Konference11th Nordic Symposium on Building Physics
Nummer11
LokationThe Electro Building at Gløshaugen campus, NTNU
LandNorge
ByTrondheim
Periode11/06/201714/06/2017
Internetadresse

Fingerprint

Air
Hatches
Chimneys
Blowers
Ceilings
Ducts
Ventilation

Citer dette

@inproceedings{394962e8af824452ab487be10492c39d,
title = "Air tightness measurements in older Danish single-family houses",
abstract = "This paper reports and discusses the air tightness of the building envelope in existing single-family houses in Denmark. The air tightness of the building envelope depends in particular on the performance of specific construction details. There is a lack of knowledge about the air tightness of the building envelope of older buildings despite the fact that the air tightness has a major influence on the energy use. In connection with renovation of the Danish building stock, the coming years will see increased focus on the air tightness of the building envelope like in other countries. This paper presents the results of measurements in 16 single-family houses built between 1880 and 2007. The air tightness of the building envelope was measured according to EN ISO 9972 using the blower-door technique. The results are compared with measurement results of the average air-change rate in the same houses measured over a period of 1-3 weeks when the houses were in normal use. The measurement results of the air tightness of the building envelope range from 1.1 to 5.8 l/(s·m²) at 50 Pa. The investigated houses are all naturally ventilated. The results of the ventilation measurements showed an outdoor air supply ranging from 0.09 to 0.28 l/(s·m²) per heated floor area, which is below the requirement stipulated in the Danish Building Regulations of 0.3 l/(s·m²).Typically, leaks are observed in connection with penetrations of the envelope, e.g. for electrical installations, exhaust ducts and chimneys. In addition, leaks are observed around older windows and doors and in connection with wooden ceilings and attic hatches. The findings should be taken into account when renovating older single-family houses.",
keywords = "Field measurements, air tightness, blower-door, leakage, ventilation rate",
author = "Mortensen, {Lone Hedegaard} and Bergs{\o}e, {Niels Christian}",
year = "2017",
month = "10",
day = "25",
doi = "10.1016/j.egypro.2017.10.016",
language = "English",
volume = "132",
pages = "825--830",
journal = "Energy Procedia",
issn = "1876-6102",
publisher = "Elsevier",

}

Air tightness measurements in older Danish single-family houses. / Mortensen, Lone Hedegaard; Bergsøe, Niels Christian.

I: Energy Procedia, Bind 132, 25.10.2017, s. 825-830.

Publikation: Bidrag til tidsskriftKonferenceartikel i tidsskriftForskningpeer review

TY - GEN

T1 - Air tightness measurements in older Danish single-family houses

AU - Mortensen, Lone Hedegaard

AU - Bergsøe, Niels Christian

PY - 2017/10/25

Y1 - 2017/10/25

N2 - This paper reports and discusses the air tightness of the building envelope in existing single-family houses in Denmark. The air tightness of the building envelope depends in particular on the performance of specific construction details. There is a lack of knowledge about the air tightness of the building envelope of older buildings despite the fact that the air tightness has a major influence on the energy use. In connection with renovation of the Danish building stock, the coming years will see increased focus on the air tightness of the building envelope like in other countries. This paper presents the results of measurements in 16 single-family houses built between 1880 and 2007. The air tightness of the building envelope was measured according to EN ISO 9972 using the blower-door technique. The results are compared with measurement results of the average air-change rate in the same houses measured over a period of 1-3 weeks when the houses were in normal use. The measurement results of the air tightness of the building envelope range from 1.1 to 5.8 l/(s·m²) at 50 Pa. The investigated houses are all naturally ventilated. The results of the ventilation measurements showed an outdoor air supply ranging from 0.09 to 0.28 l/(s·m²) per heated floor area, which is below the requirement stipulated in the Danish Building Regulations of 0.3 l/(s·m²).Typically, leaks are observed in connection with penetrations of the envelope, e.g. for electrical installations, exhaust ducts and chimneys. In addition, leaks are observed around older windows and doors and in connection with wooden ceilings and attic hatches. The findings should be taken into account when renovating older single-family houses.

AB - This paper reports and discusses the air tightness of the building envelope in existing single-family houses in Denmark. The air tightness of the building envelope depends in particular on the performance of specific construction details. There is a lack of knowledge about the air tightness of the building envelope of older buildings despite the fact that the air tightness has a major influence on the energy use. In connection with renovation of the Danish building stock, the coming years will see increased focus on the air tightness of the building envelope like in other countries. This paper presents the results of measurements in 16 single-family houses built between 1880 and 2007. The air tightness of the building envelope was measured according to EN ISO 9972 using the blower-door technique. The results are compared with measurement results of the average air-change rate in the same houses measured over a period of 1-3 weeks when the houses were in normal use. The measurement results of the air tightness of the building envelope range from 1.1 to 5.8 l/(s·m²) at 50 Pa. The investigated houses are all naturally ventilated. The results of the ventilation measurements showed an outdoor air supply ranging from 0.09 to 0.28 l/(s·m²) per heated floor area, which is below the requirement stipulated in the Danish Building Regulations of 0.3 l/(s·m²).Typically, leaks are observed in connection with penetrations of the envelope, e.g. for electrical installations, exhaust ducts and chimneys. In addition, leaks are observed around older windows and doors and in connection with wooden ceilings and attic hatches. The findings should be taken into account when renovating older single-family houses.

KW - Field measurements

KW - air tightness

KW - blower-door

KW - leakage

KW - ventilation rate

UR - http://sbi.dk/Pages/Taethed-af-klimaskaermen-i-eksisterende-boliger.aspx

U2 - 10.1016/j.egypro.2017.10.016

DO - 10.1016/j.egypro.2017.10.016

M3 - Conference article in Journal

VL - 132

SP - 825

EP - 830

JO - Energy Procedia