Abstract
This paper addresses the modular multilevel converter applied as a static synchronous compensator. The main objective of this work is to compare the converter performance considering two different submodule capacitor voltage balancing strategies: nearest level control and phase-shifted pulse width modulation, during positive and negative sequence current injection. Results of a 15 MVA MMC STATCOM show that the nearest level control strategy has lower average switching frequency compared to the phase-shifted pulse width modulation strategy, considering comparable submodule capacitance voltage ripple.
Originalsprog | Engelsk |
---|---|
Titel | Proceedings of the 18th European Conference on Power Electronics and Applications (EPE'16 ECCE Europe) |
Antal sider | 9 |
Forlag | IEEE |
Publikationsdato | sep. 2016 |
ISBN (Elektronisk) | 978-9-0758-1524-5 |
DOI | |
Status | Udgivet - sep. 2016 |
Begivenhed | EPE'16 - ECCE: 18th European Conference on Power Electronics and Applications - Karlsruhe Town Hall (Stadthalle), Karlsruhe, Tyskland Varighed: 5 sep. 2016 → 9 sep. 2016 Konferencens nummer: 18 http://www.epe2016.com/ |
Konference
Konference | EPE'16 - ECCE: 18th European Conference on Power Electronics and Applications |
---|---|
Nummer | 18 |
Lokation | Karlsruhe Town Hall (Stadthalle) |
Land/Område | Tyskland |
By | Karlsruhe |
Periode | 05/09/2016 → 09/09/2016 |
Internetadresse |