In commercial chilled water systems, one of the most prevalent system topology is the Primary/Secondary topology. In this topology, the primary and secondary circuits of the hydronic cooling system are hydraulically decoupled by a common pipe also referred to as the bypass. This allows the primary circuit to ensure minimum chiller flow without interfering with the secondary side. To maximize heat transfer and achieve optimal performance, the flow in the primary and secondary systems must equalize and thus leave no flow in the bypass line when the minimum chiller flow requirement is fulfilled. To achieve this goal in a robust and responsive manner a simple and cost-effective feedback method is proposed, where 3 temperature sensors constitute the control feedback for the primary pump control. Closed-loop stability is proven and automatic sensor calibration is proposed. The method is verified through lab test on a setup emulating by-pass of the Primary/Secondary topology.

OriginalsprogEngelsk
TitelCCTA 2021 - 5th IEEE Conference on Control Technology and Applications
Antal sider6
ForlagIEEE
Publikationsdato2021
Sider1166-1171
ISBN (Trykt)978-1-6654-3644-1
ISBN (Elektronisk)978-1-6654-3643-4
DOI
StatusUdgivet - 2021
Begivenhed5th IEEE Conference on Control Technology and Applications, CCTA 2021 - Virtual, San Diego, USA
Varighed: 8 aug. 202111 aug. 2021

Konference

Konference5th IEEE Conference on Control Technology and Applications, CCTA 2021
Land/OmrådeUSA
ByVirtual, San Diego
Periode08/08/202111/08/2021
SponsorIEEE Conference on Decision and Control (CDC), IEEE Control Systems Society (CSS)
NavnIEEE Conference on Control Technology and Applications (CCTA) - Proceedings
ISSN2768-0762

Bibliografisk note

Publisher Copyright:
© 2021 IEEE.

Fingeraftryk

Dyk ned i forskningsemnerne om 'Chiller Pump Control using Temperature Sensor Feedback'. Sammen danner de et unikt fingeraftryk.

Citationsformater