Abstract
This paper presents a comparative analysis of a static synchronous compensator (STATCOM) based on battery energy storage system with grid-following and grid-forming operations utilized for stability enhancement of offshore wind power plants (WPPs). The small-signal model of a typical offshore WPP system is developed first, then compared from two perspectives – oscillation index for stability margin evaluation of a multi-input multi-output system and damping ratio of dominant poles, with respect to the critical control parameters. The theoretical comparative analysis proves that the grid-forming control offers evident stability margin and damping to the WPPs especially in weak grids, superior to the grid-following STATCOM. This conclusion holds true for most conditions with properly designed parameters, including different bandwidths of the alternating voltage control of STATCOM in 1∼10 Hz and phase-locked loop of grid-following STATCOM ranging from 5 to 100 Hz, which is benefited from the sufficient stability margin of GFM mode. The small-signal models and comparative analysis are corroborated by electromagnetic transients (EMT) simulations.
Originalsprog | Engelsk |
---|---|
Artikelnummer | 108449 |
Tidsskrift | Electric Power Systems Research |
Vol/bind | 212 |
ISSN | 0378-7796 |
DOI | |
Status | Udgivet - nov. 2022 |
Bibliografisk note
Publisher Copyright:© 2022 Elsevier B.V.