Comparison of PI and PR current controllers applied on two-level VSC-HVDC transmission system

A. Manoloiu, H.A. Pereria, Remus Teodorescu, M. Bongiorno, M. Eremia, S.R. Silva

Publikation: Bidrag til bog/antologi/rapport/konference proceedingKonferenceartikel i proceedingForskningpeer review

5 Citationer (Scopus)

Abstrakt

This paper analyzes differences between αβ and dq reference frames regarding the control of two-level VSC-HVDC current loop and dc-link voltage outer loop. In the first part, voltage feedforward effect is considered with PI and PR controllers. In the second part, the feedforward effect is removed and the PR gains are tuned to keep the dynamic performance. Also, the power feedforward is removed and the outer loop PI controller is tuned in order to maintain the system dynamic performance. The paper is completed with simulation results, which highlight the advantages of using PR controller.
OriginalsprogEngelsk
TitelPowerTech, 2015 IEEE Eindhoven
Antal sider5
ForlagIEEE Press
Publikationsdato31 aug. 2015
Sider1-5
Artikelnummer7232648
ISBN (Trykt)978-147997693-5
DOI
StatusUdgivet - 31 aug. 2015
BegivenhedIEEE Eindhoven PowerTech, PowerTech 2015 - Eindhoven, Holland
Varighed: 29 jun. 20152 jul. 2015

Konference

KonferenceIEEE Eindhoven PowerTech, PowerTech 2015
LandHolland
ByEindhoven
Periode29/06/201502/07/2015

Fingeraftryk Dyk ned i forskningsemnerne om 'Comparison of PI and PR current controllers applied on two-level VSC-HVDC transmission system'. Sammen danner de et unikt fingeraftryk.

  • Citationsformater

    Manoloiu, A., Pereria, H. A., Teodorescu, R., Bongiorno, M., Eremia, M., & Silva, S. R. (2015). Comparison of PI and PR current controllers applied on two-level VSC-HVDC transmission system. I PowerTech, 2015 IEEE Eindhoven (s. 1-5). [7232648] IEEE Press. https://doi.org/10.1109/PTC.2015.7232648