The Low-Voltage Ride-Through (LVRT) has become an important grid requirement for offshore wind farms connecting with Voltage Source Converter based High Voltage Direct Current (VSC-HVDC) links. In this paper, a cooperative control strategy with LVRT ability is proposed for a VSC-HVDC connected variable speed Squirrel-Cage Induction Generator (SCIG) wind farm. The approach employs a DC-link voltage versus offshore AC-bus frequency droop control on the offshore converter of VSC-HVDC link. Thus, the back-to-back converters of SCIG wind turbines can adjust the generated active power based on the AC-bus frequency deviations, so that a fast power reduction on the wind farm side can be achieved. The EMTDC/PSCAD simulations are performed on a 300 MW offshore variable speed SCIG wind farm. Simulation results confirm the effectiveness of the proposed control method.
OriginalsprogEngelsk
TitelProceedings of the 2012 IEEE International Power System Technology (POWERCON)
Antal sider6
ForlagIEEE Press
Publikationsdato2012
Sider1-6
ISBN (Trykt)978-1-4673-2868-5
DOI
StatusUdgivet - 2012
BegivenhedPower System Technology (POWERCON), 2012 IEEE International Conference on (POWERCON), 2012 IEEE International Conference on - Auckland, New Zealand
Varighed: 30 okt. 20122 nov. 2012

Konference

KonferencePower System Technology (POWERCON), 2012 IEEE International Conference on (POWERCON), 2012 IEEE International Conference on
Land/OmrådeNew Zealand
ByAuckland
Periode30/10/201202/11/2012

Fingeraftryk

Dyk ned i forskningsemnerne om 'Cooperative control of VSC-HVDC connected offshore wind farm with Low-Voltage Ride-Through capability'. Sammen danner de et unikt fingeraftryk.

Citationsformater