Abstract
The Low-Voltage Ride-Through (LVRT) has become an important grid requirement for offshore wind farms connecting with Voltage Source Converter based High Voltage Direct Current (VSC-HVDC) links. In this paper, a cooperative control strategy with LVRT ability is proposed for a VSC-HVDC connected variable speed Squirrel-Cage Induction Generator (SCIG) wind farm. The approach employs a DC-link voltage versus offshore AC-bus frequency droop control on the offshore converter of VSC-HVDC link. Thus, the back-to-back converters of SCIG wind turbines can adjust the generated active power based on the AC-bus frequency deviations, so that a fast power reduction on the wind farm side can be achieved. The EMTDC/PSCAD simulations are performed on a 300 MW offshore variable speed SCIG wind farm. Simulation results confirm the effectiveness of the proposed control method.
Originalsprog | Engelsk |
---|---|
Titel | Proceedings of the 2012 IEEE International Power System Technology (POWERCON) |
Antal sider | 6 |
Forlag | IEEE Press |
Publikationsdato | 2012 |
Sider | 1-6 |
ISBN (Trykt) | 978-1-4673-2868-5 |
DOI | |
Status | Udgivet - 2012 |
Begivenhed | Power System Technology (POWERCON), 2012 IEEE International Conference on (POWERCON), 2012 IEEE International Conference on - Auckland, New Zealand Varighed: 30 okt. 2012 → 2 nov. 2012 |
Konference
Konference | Power System Technology (POWERCON), 2012 IEEE International Conference on (POWERCON), 2012 IEEE International Conference on |
---|---|
Land/Område | New Zealand |
By | Auckland |
Periode | 30/10/2012 → 02/11/2012 |