Coordination between Fault-Ride-Through Capability and Over-current Protection of DFIG Generators for Wind Farms

Birgitte Bak-Jensen, T.A. Kawady, Mansour Hassan Abdel-Rahman

Publikation: Bidrag til tidsskriftTidsskriftartikelForskningpeer review

2594 Downloads (Pure)

Abstract

Fault Ride-Through (FRT) capabilities set up according to the grid codes may affect the performance of related protective elements during fault periods. Therefore, in this paper the coordination between the FRT capability and over-current protection of DFIG Wind Generators in MV networks is investigated. Simulation test cases using MATLAB-Simulink are implemented on a 365-MW wind farm in AL-Zaafarana, Egypt. The simulation results show the influence of the FRT capability on the protective relaying coordination in wind farms, showing that the FRT may work in situations where is were expected not to work, and then disabling the over-current protection, which should have worked in this situation.
OriginalsprogEngelsk
TidsskriftJournal of Energy and Power Engineering
Vol/bind4
Udgave nummer4
Sider (fra-til)20-29
Antal sider10
ISSN1934-8975
StatusUdgivet - apr. 2010