Coordination of Voltage and Frequency Feedback in Load-Frequency Control Capability of Wind Turbine

Bakhtyar Hoseinzadeh, Filipe Faria Da Silva, Claus Leth Bak

Publikation: Bidrag til bog/antologi/rapport/konference proceedingKonferenceartikel i proceedingForskningpeer review

5 Citationer (Scopus)

Abstract

In close future, with high Wind Energy (WE) penetration in the power system, the burden of Load-Frequency Control (LFC) is gradually shifted to Variable Speed Wind Turbines (VSWTs). In order to equip the VSWT with LFC capability to support the grid during sudden variation in generation or load, sufficient reserve capacity should be procured. This paper addresses the Load-Frequency Control (LFC) scheme offered by VSWT. Feedback loop of locally measured voltage and frequency data is employed to improve transient and permanent response to achieve faster and more efficient LFC action and voltage regulation. The proposed scheme demonstrates remarkable improvement transient state of both voltage and frequency profiles in comparison with conventional LFC designs provided by Central Power Plants (CPP) or Wind Power Plants (WPP). Numerical simulations carried out in DigSilent Power- Factory confirm the superiority of proposed methodology used in Permanent Magnet Synchronous Machine (PMSG) connected to 9-bus IEEE standard test system.
OriginalsprogEngelsk
TitelProceedings of the 40th Annual Conference of IEEE Industrial Electronics Society, IECON 2014
Antal sider7
ForlagIEEE Press
Publikationsdatonov. 2014
Sider5501 - 5507
ISBN (Trykt)978-1-4799-3960-2
DOI
StatusUdgivet - nov. 2014
Begivenhed40th Annual Conference of IEEE Industrial Electronics Society - Dallas, TX, USA
Varighed: 29 okt. 20141 nov. 2014

Konference

Konference40th Annual Conference of IEEE Industrial Electronics Society
Land/OmrådeUSA
ByDallas, TX
Periode29/10/201401/11/2014