Experimental Study of an Integrated System with Diffuse Ceiling Ventilation and Thermally Activated Building Constructions

Publikation: Bog/antologi/afhandling/rapportRapportForskning

344 Downloads (Pure)

Resumé

The experiments are carried out in a climate chamber located at the Department of Civil Engineering Aalborg University. The objective of the experiments is to evaluate the performance of the system combining diffuse ceiling ventilation and thermally activated building construction (TABS) in terms of thermal comfort and energy performance. 20 cases with different boundary conditions are conducted varying on climate condition heat load. TABS water temperature and flow rate with or without diffuse ceiling. The energy evaluation includes energy balance of test room and cooling or heating capacity of TABS. And the thermal comfort is analyzed by draught rate vertical temperature gradient and radiant temperature asymmetry. Finally the effect of plenum and diffuse ceiling is discussed.

This report mainly focuses on the experiment results and discussions. Therefore, some details about the measurement are not presented in this report but can be found in the experimental plan made before.
OriginalsprogEngelsk
Udgivelses stedAalborg
ForlagDepartment of Civil Engineering, Aalborg University
Antal sider33
StatusUdgivet - 2014
NavnDCE Technical reports
Nummer182
ISSN1901-726X

Fingerprint

Ceilings
Ventilation
Thermal comfort
Experiments
Thermal load
Civil engineering
Energy balance
Thermal energy
Thermal gradients
Flow rate
Boundary conditions
Cooling
Heating
Temperature
Water

Bibliografisk note

Pdf for print: 39 pp.

Emneord

  • Ventilation
  • Diffuse ceiling ventilation
  • Building constructions
  • Thermally activated building system
  • Experimental study

Citer dette

Zhang, Chen ; Yu, Tao ; Heiselberg, Per ; Pomianowski, Michal Zbigniew. / Experimental Study of an Integrated System with Diffuse Ceiling Ventilation and Thermally Activated Building Constructions. Aalborg : Department of Civil Engineering, Aalborg University, 2014. 33 s. (DCE Technical reports; Nr. 182).
@book{3a960bb05a7344c0a88e4eee4dd22f24,
title = "Experimental Study of an Integrated System with Diffuse Ceiling Ventilation and Thermally Activated Building Constructions",
abstract = "The experiments are carried out in a climate chamber located at the Department of Civil Engineering Aalborg University. The objective of the experiments is to evaluate the performance of the system combining diffuse ceiling ventilation and thermally activated building construction (TABS) in terms of thermal comfort and energy performance. 20 cases with different boundary conditions are conducted varying on climate condition heat load. TABS water temperature and flow rate with or without diffuse ceiling. The energy evaluation includes energy balance of test room and cooling or heating capacity of TABS. And the thermal comfort is analyzed by draught rate vertical temperature gradient and radiant temperature asymmetry. Finally the effect of plenum and diffuse ceiling is discussed.This report mainly focuses on the experiment results and discussions. Therefore, some details about the measurement are not presented in this report but can be found in the experimental plan made before.",
keywords = "Ventilation, Diffuse ceiling ventilation, Building constructions, Thermally activated building system, Experimental study, Ventilation, Diffuse ceiling ventilation, Building constructions, Thermally activated building system, Experimental study",
author = "Chen Zhang and Tao Yu and Per Heiselberg and Pomianowski, {Michal Zbigniew}",
note = "Pdf for print: 39 pp.",
year = "2014",
language = "English",
series = "DCE Technical reports",
publisher = "Department of Civil Engineering, Aalborg University",
number = "182",
address = "Denmark",

}

Zhang, C, Yu, T, Heiselberg, P & Pomianowski, MZ 2014, Experimental Study of an Integrated System with Diffuse Ceiling Ventilation and Thermally Activated Building Constructions. DCE Technical reports, nr. 182, Department of Civil Engineering, Aalborg University, Aalborg.

Experimental Study of an Integrated System with Diffuse Ceiling Ventilation and Thermally Activated Building Constructions. / Zhang, Chen; Yu, Tao; Heiselberg, Per; Pomianowski, Michal Zbigniew.

Aalborg : Department of Civil Engineering, Aalborg University, 2014. 33 s. (DCE Technical reports; Nr. 182).

Publikation: Bog/antologi/afhandling/rapportRapportForskning

TY - RPRT

T1 - Experimental Study of an Integrated System with Diffuse Ceiling Ventilation and Thermally Activated Building Constructions

AU - Zhang, Chen

AU - Yu, Tao

AU - Heiselberg, Per

AU - Pomianowski, Michal Zbigniew

N1 - Pdf for print: 39 pp.

PY - 2014

Y1 - 2014

N2 - The experiments are carried out in a climate chamber located at the Department of Civil Engineering Aalborg University. The objective of the experiments is to evaluate the performance of the system combining diffuse ceiling ventilation and thermally activated building construction (TABS) in terms of thermal comfort and energy performance. 20 cases with different boundary conditions are conducted varying on climate condition heat load. TABS water temperature and flow rate with or without diffuse ceiling. The energy evaluation includes energy balance of test room and cooling or heating capacity of TABS. And the thermal comfort is analyzed by draught rate vertical temperature gradient and radiant temperature asymmetry. Finally the effect of plenum and diffuse ceiling is discussed.This report mainly focuses on the experiment results and discussions. Therefore, some details about the measurement are not presented in this report but can be found in the experimental plan made before.

AB - The experiments are carried out in a climate chamber located at the Department of Civil Engineering Aalborg University. The objective of the experiments is to evaluate the performance of the system combining diffuse ceiling ventilation and thermally activated building construction (TABS) in terms of thermal comfort and energy performance. 20 cases with different boundary conditions are conducted varying on climate condition heat load. TABS water temperature and flow rate with or without diffuse ceiling. The energy evaluation includes energy balance of test room and cooling or heating capacity of TABS. And the thermal comfort is analyzed by draught rate vertical temperature gradient and radiant temperature asymmetry. Finally the effect of plenum and diffuse ceiling is discussed.This report mainly focuses on the experiment results and discussions. Therefore, some details about the measurement are not presented in this report but can be found in the experimental plan made before.

KW - Ventilation

KW - Diffuse ceiling ventilation

KW - Building constructions

KW - Thermally activated building system

KW - Experimental study

KW - Ventilation

KW - Diffuse ceiling ventilation

KW - Building constructions

KW - Thermally activated building system

KW - Experimental study

M3 - Report

T3 - DCE Technical reports

BT - Experimental Study of an Integrated System with Diffuse Ceiling Ventilation and Thermally Activated Building Constructions

PB - Department of Civil Engineering, Aalborg University

CY - Aalborg

ER -

Zhang C, Yu T, Heiselberg P, Pomianowski MZ. Experimental Study of an Integrated System with Diffuse Ceiling Ventilation and Thermally Activated Building Constructions. Aalborg: Department of Civil Engineering, Aalborg University, 2014. 33 s. (DCE Technical reports; Nr. 182).