GPS-synchronized harmonic measurements performed on a 400kV transmission network

Wojciech Wiechowski*, Jan Lykkegaard, Birgitte Bak-Jensen, Claus Leth Bak, Jacek Wasilewski

*Kontaktforfatter

Publikation: Bidrag til bog/antologi/rapport/konference proceedingKonferenceartikel i proceedingForskningpeer review

Abstract

In this paper, GPS-synchronized harmonic measurements performed on the transmission network of the Danish TSO Energinet.dk are presented. The purpose of the measurements was to verify a computer model of the network. The selected verification method was based on determination of transfer harmonic impedance by switching a series component that contains a shunt branch [1], [2]. Harmonic currents and voltages were simultaneously measured at three 400kV substations with OMICRON CMC256 units with EnerLyzer function and GPS synchronization units. Time domain "snapshot" measurements of three-phase voltages and currents were synchronously taken, while a power line was switched out and in, and the results were post-processed in Matlab. Harmonic voltages were measured using capacitive taps of the 400kV/150kV autotransformer bushings. Harmonic currents were measured as voltage drop on low-inductance resistors inserted in series with the metering equipment. Due to largely unbalanced harmonic currents, the computer network model was verified by a modified verification method, based on injection of measured harmonic currents and comparison of resultant voltage increments. The method requires precise synchronization of the units and sufficient level of harmonic distortion in the network.
OriginalsprogEngelsk
Titel2007 9th International Conference on Electrical Power Quality and Utilisation, EPQU
Publikationsdatodec. 2007
Artikelnummer4424111
ISBN (Trykt)8469100572, 9788469100578
DOI
StatusUdgivet - dec. 2007
Begivenhed2007 9th International Conference on Electrical Power Quality and Utilisation, EPQU - Barcelona, Spanien
Varighed: 9 okt. 200711 okt. 2007

Konference

Konference2007 9th International Conference on Electrical Power Quality and Utilisation, EPQU
Land/OmrådeSpanien
ByBarcelona
Periode09/10/200711/10/2007

Fingeraftryk

Dyk ned i forskningsemnerne om 'GPS-synchronized harmonic measurements performed on a 400kV transmission network'. Sammen danner de et unikt fingeraftryk.

Citationsformater