Abstract
Following work examines current and voltage distribution during ground faults in cables of the transformer-less feeder system consisting of interconnected voltage source converters. Analysis is performed with regard to converter block operation, fault-ride-through requirements, cable design and different grounding schemes. Analysis show, that systems with effective grounded generator's neutral in general provide best ground current and voltage distribution across cables.
| Originalsprog | Engelsk |
|---|---|
| Titel | Proceedings of the 15th European Conference on Power Electronics and Applications, EPE 2013 |
| Antal sider | 10 |
| Forlag | IEEE Press |
| Publikationsdato | 2013 |
| Sider | 1-10 |
| ISBN (Trykt) | 9781479901159 |
| ISBN (Elektronisk) | 978-147990116-6, 9781479901142 |
| DOI | |
| Status | Udgivet - 2013 |
| Begivenhed | EPE'13 ECCE Europe 15th European Conference on Power Electronics and Applications - Lille, Frankrig Varighed: 3 sep. 2013 → 5 sep. 2013 http://www.epe2013.com/ |
Konference
| Konference | EPE'13 ECCE Europe 15th European Conference on Power Electronics and Applications |
|---|---|
| Land/Område | Frankrig |
| By | Lille |
| Periode | 03/09/2013 → 05/09/2013 |
| Internetadresse |
Fingeraftryk
Dyk ned i forskningsemnerne om 'Grounding System Studies for Transformer-less Collector Feeder of Full-Scale Power Converters'. Sammen danner de et unikt fingeraftryk.Citationsformater