Abstract
Based on the analysis of a specific relay model and an HVAC (High Voltage Alternating Current) cable system, a new approach to EMTDC/PSCAD modelling of protective relays is presented. Such approach allows creating complex and accurate relay models derived from the original algorithms. Relay models can be applied with various systems, allowing obtaining the most optimal configuration of the protective relaying. The present paper describes modelling methodology on the basis of Siemens SIPROTEC 4 7SD522/610. Relay model was verified experimentally with its real equivalent by both EMTP-simulated and real world generated current signals connected to the relay.
Originalsprog | Engelsk |
---|---|
Titel | Proceedings of the International Protection Testing Symposium 2011 |
Antal sider | 7 |
Forlag | OMICRON |
Publikationsdato | 2011 |
Status | Udgivet - 2011 |
Begivenhed | International Protection Testing Symposium 2011 - Brand, Østrig Varighed: 4 okt. 2011 → 6 okt. 2011 |
Konference
Konference | International Protection Testing Symposium 2011 |
---|---|
Land/Område | Østrig |
By | Brand |
Periode | 04/10/2011 → 06/10/2011 |