Negative sequence current control in wind power plants with VSC-HVDC connection

Sanjay Chaudhary, Remus Teodorescu, Pedro Rodriguez, Philip Carne Kjaer, Ani M. Gole

Publikation: Bidrag til tidsskriftTidsskriftartikelForskningpeer review

106 Citationer (Scopus)

Abstract

Large offshore wind power plants may have multi-MW wind turbine generators (WTG) equipped with full-scale converters (FSC) and voltage source converter (VSC) based high voltaage direct-current (HVDC) transmission for grid
connection. The power electronic converters in theWTG-FSC and the VSC-HVDC allow fast current control in the offshore grid. This paper presents a method of controlling the negative sequence current injection into the offshore grid from the VSC-HVDC as well as WTG-FSCs. This would minimize the power oscillations and hence reduce the dc voltage overshoots in the VSC-HVDC system as well as in the WTG-FSCs; especially when the offshore grid is unbalanced due to asymmetric faults. The formulation for negative sequence current injection is mathematically derived and then implemented in electromagnetic transients (EMT) simulation model. The simulated results show that the negative sequence
current control mitigates the power oscillations and therefore limits the dc voltage excursions in the VSC-HVDC system during the asymmetric faults.
OriginalsprogEngelsk
TidsskriftI E E E Transactions on Sustainable Energy
Vol/bind3
Udgave nummer3
Sider (fra-til)535-544
Antal sider10
ISSN1949-3029
DOI
StatusUdgivet - jul. 2012

Fingeraftryk

Dyk ned i forskningsemnerne om 'Negative sequence current control in wind power plants with VSC-HVDC connection'. Sammen danner de et unikt fingeraftryk.