Novel differential protection based on the ratio of model error indices in time-domain for transmission cable system

Publikation: Bidrag til tidsskriftTidsskriftartikelForskningpeer review

Abstrakt

The significant shunt parameters of underground cable (UC) systems, as well as the frequently-used shunt reactor, draw many attentions in the implementation of the differential relay. In this paper, a novel ratio of model error indices (RMEIs) based differential protection (RMEIDP) scheme is proposed. The internal/external faults lead to different fault component networks, from which the proposed RMEIDP distinguishes the fault states by identifying the corresponding fault component models. The RMEIDP scheme, incorporating both the external fault differential model and the internal one, is theoretically unaffected by the cable charging current and weakens the impacts of shunt reactor. What’s more, the proposed RMEIDP scheme is adaptive for not only the fault steady state but also the fault transient state, since the time-domain fault information is directly used in the model error index (MEI) computation. DIgSILENT-based EMT simulation results of the UC transmission system prove the effectiveness and merits of the new differential relay scheme.
OriginalsprogEngelsk
Artikelnummer106077
TidsskriftElectric Power Systems Research
Vol/bind180
Antal sider10
ISSN0378-7796
DOI
StatusUdgivet - mar. 2020

Fingeraftryk Dyk ned i forskningsemnerne om 'Novel differential protection based on the ratio of model error indices in time-domain for transmission cable system'. Sammen danner de et unikt fingeraftryk.

  • Citationsformater