Optimization of night ventilation performance in office buildings in a cold climate

Rui Guo*, Per Heiselberg, Yue Hu, Chen Zhang, Sandijs Vasilevskis

*Kontaktforfatter

Publikation: Bidrag til tidsskriftTidsskriftartikelForskningpeer review

23 Citationer (Scopus)
39 Downloads (Pure)

Abstract

The rising cooling demand and overheating in the building sector, especially in office buildings, have intensified research interest in recent years. Night ventilation (NV) as a passive energy technology has shown a great potential cooling energy and ameliorate indoor thermal environment. In this paper, a holistic approach involving global sensitivity analysis and evolutionary optimization is developed to exclude insignificant parameters and explore optimal NV performance in terms of energy use and thermal comfort. The proposed approach is based on the simulation research of a three-story office building equipped with daytime air conditioning and NV system in a cold climate region. The NV system is equipped with three levels of specific fan power (SFP), representing cases with natural NV and medium and high SFP mechanical NV, respectively. The results show that the activation threshold temperature is not the key parameter for NV performance. Comparing with the case without NV, the three SFP NV systems under a general scheme save 8.8% to 82.5% total cooling energy consumption (TCEC), but increase the average percentage of dissatisfied during occupied hours (aPPD) from 7.5% to about 15%, which may cause overcooling penalty. The optimization decreases the thermal mass area and the night air change rate setpoint at each hour, while increases the minimum indoor air temperature setpoint compared to the general scheme. All three optimal NV schemes significantly improve the indoor thermal comfort by maintaining the aPPD at 7.5%. The optimal medium and high SFP mechanical NV scheme further save 7.1% and 38.6% TCEC compared to the corresponding general mechanical NV scheme, respectively. With a higher SFP, a greater energy saving potential is contributed through NV optimization process. Even though the optimal natural NV scheme consumes more than twice as much TCEC as the general natural NV scheme, it is still worth optimizing the natural NV since the indoor thermal comfort can be improved and the optimal scheme still saves much cooling energy compared to the base case.

OriginalsprogEngelsk
Artikelnummer110319
TidsskriftEnergy and Buildings
Vol/bind225
Udgave nummerOctober
Antal sider13
ISSN0378-7788
DOI
StatusUdgivet - 15 okt. 2020

Fingeraftryk

Dyk ned i forskningsemnerne om 'Optimization of night ventilation performance in office buildings in a cold climate'. Sammen danner de et unikt fingeraftryk.

Citationsformater