Abstract
Highlights
•The push-pull ventilation system is proposed to improve IAQ inside kitchen, where air is supplied through slot air curtain and then exhausted through range hood.
•CO2 reduction efficiency with application of air curtain in experiment and simulation in breathing zone was 23.7% and 23.1%, respectively.
•By orthogonal method, the influence of factors on pollution control of the push-pull ventilation system was presented.
•The push-pull ventilation system is proposed to improve IAQ inside kitchen, where air is supplied through slot air curtain and then exhausted through range hood.
•CO2 reduction efficiency with application of air curtain in experiment and simulation in breathing zone was 23.7% and 23.1%, respectively.
•By orthogonal method, the influence of factors on pollution control of the push-pull ventilation system was presented.
Originalsprog | Engelsk |
---|---|
Tidsskrift | Building and Environment |
Vol/bind | 107 |
Sider (fra-til) | 99–112 |
Antal sider | 14 |
ISSN | 0360-1323 |
DOI | |
Status | Udgivet - 2016 |
Emneord
- Kitchen ventilation
- Air distribution
- Air curtain
- Pollution control