Abstract
This test report contains descriptions and results for 3 tests carried out at the Structural Research Laboratory at Aalborg University. The aims of the tests were to find the strength of a section of a special connection between a wind turbine and its foundations. In this connection the material Ducorit D4 from Densit A/S was used to connect the reinforcement bars of the foundations with the steel tower of the wind turbine. The 3 tests described in this report are additional tests. The primary tests are described in Jensen, J. N. & Pedersen, C. H., 2005. The difference between these tests and the primary tests is that the Ducorit D4 is reinforced with small steel fibres (2%) in these additional tests. The test specimens and the test setup are described in detail by Jensen, J. N. & Pedersen, C. H., 2005.
There is only a short description in this report.
3 Ducorit cylinders were tested to determine the ultimate strength and the modulus of elasticity. The diameter of the cylinders was 100 mm and the height was 200 mm.
There is only a short description in this report.
3 Ducorit cylinders were tested to determine the ultimate strength and the modulus of elasticity. The diameter of the cylinders was 100 mm and the height was 200 mm.
Originalsprog | Engelsk |
---|
Udgivelsessted | Aalborg |
---|---|
Forlag | Dept. of Building Technology and Structural Engineering, Aalborg University |
Antal sider | 12 |
Status | Udgivet - aug. 2005 |
Navn | Aalborg Universitet. Instituttet for Bygningsteknik. R |
---|---|
Nummer | R0506 |
ISSN | 1395-7953 |
Bibliografisk note
Test report.PDF for print : 12 pp.