Renewable energy sources are getting more and more widespread, mainly due to the fact that they generate energy by keeping the environment clean. Most of these systems have an isolation transformer included, which if excluded from the system would increase the efficiency and decrease the size of PV installations, furthermore it would lead to a lower cost for the whole investment. But there are some safety issues regarding the missing galvanic isolation. This paper is aiming to analyze and compare the most common single-stage transformerless PV inverter topologies for single-phase and three-phase with respect to the leakage current generation. The best results, both for single-phase and three-phase systems, are obtained when the middle point of the input capacitors is connected to the neutral point, thereby minimizing the voltage fluctuations present at the terminals of the PV panel.