title = "Wide Area Protection Scheme Preventing Cascading Events Caused by Load Flow Transferring",
abstract = "Load flow transferring after an initial contingency is regarded as one of the main reasons of causing unexpected cascading trips. A multi agent system (MAS) based wide area protection strategy is proposed in this paper to predict the load flow transferring from the point of view of impedance relays, and prevent the unexpected relay operations accordingly. The variations of node injections during the post fault transient period will be also considered in the prediction algorithm. The power system of Eastern Denmark modeled in real time digital simulator (RTDS) will be used to demonstrate the proposed strategy. The simulation results indicate this strategy can successfully predict and prevent the unexpected relay operation caused by load flow transferring.",
keywords = "Cascading trips, Load flow transferring, Multi agent system, Wide area protection",
author = "Zhou Liu and Zhe Chen and Haishun Sun and Yanting Hu",
year = "2013",
doi = "10.1109/PESMG.2013.6672969",
language = "English",
series = "IEEE Power and Energy Society General Meeting",
publisher = "IEEE Press",
booktitle = "Proceedings of the 2013 IEEE Power and Energy Society General Meeting (PES)",
note = "IEEE Power and Energy Society General Meeting, PES 2013 ; Conference date: 21-07-2013 Through 25-07-2013",
}