Abstract
In this paper, a method for the parallel operation of inverters in an ac-distributed system is proposed. The paper explores the control of active and reactive power flow through the analysis of the output impedance of the inverters and its impact on the power sharing. As a result, adaptive virtual output impedance is proposed in order to achieve a proper reactive power sharing regardless of the line impedance unbalances. A soft-start operation is also included, avoiding the initial current peak, which results in a seamless hot-swap operation. Active power sharing is achieved by adjusting the frequency in load transient situations only, thanks to which the proposed method obtains constant steady-state frequency and amplitude. As opposed to the conventional droop method, the transient response can be modified by acting on the main control parameters. Linear and nonlinear loads can be properly shared due to the addition of a current harmonic loop in the control strategy. Experimental results are presented from a two 6-kVA parallel-connected inverters system, showing the feasibility of the proposed approach.
Originalsprog | Engelsk |
---|---|
Titel | Proceedings of the IEEE International Symposium on Industrial Electronics 2005, ISIE 2005 |
Antal sider | 6 |
Vol/bind | II |
Publikationsdato | 1 dec. 2005 |
Sider | 845-850 |
Artikelnummer | 1529025 |
ISBN (Trykt) | 0780387384, 9780780387386 |
DOI | |
Status | Udgivet - 1 dec. 2005 |
Udgivet eksternt | Ja |
Begivenhed | IEEE International Symposium on Industrial Electronics 2005, ISIE 2005 - Dubrovnik, Kroatien Varighed: 20 jun. 2005 → 23 jun. 2005 |
Konference
Konference | IEEE International Symposium on Industrial Electronics 2005, ISIE 2005 |
---|---|
Land/Område | Kroatien |
By | Dubrovnik |
Periode | 20/06/2005 → 23/06/2005 |