Analysis and Active Damping of Multiple High Frequency Resonances in DFIG System

Research output: Contribution to journalJournal articleResearchpeer-review

18 Citations (Scopus)
240 Downloads (Pure)

Abstract

As the wind power generation develops, the Doubly Fed Induction Generator (DFIG) based wind power system are more and more likely to operate in the emerging weak network rather than the conventional stiff network. Due to the comparatively large impedance of the weak network than the stiff grid, the DFIG system may be subject to the resonances due to the impedance interaction between the DFIG system and the weak network. Especially, when connected to a series π sections weak network, the Multiple High Frequency Resonances (MHFR) may occur and require careful studies. The impedance modeling of the DFIG system and the series π sections weak network is firstly demonstrated in this paper. Then, due to the multiple magnitude peaks of the series π sections of the weak network, the MHFR will be produced and can be theoretically explained based on the impedance modeling results. For the purpose of mitigating the MHFR, an active damping strategy which introduces a virtual impedance, including a phase leading compensation unit and a virtual positive resistance, is proposed and demonstrated. Simulations are conducted to validate the DFIG system MHFR as well as the proposed active damping strategy.
Original languageEnglish
JournalI E E E Transactions on Energy Conversion
Volume32
Issue number1
Pages (from-to)369-381
Number of pages13
ISSN0885-8969
DOIs
Publication statusPublished - Mar 2017

Keywords

  • DFIG system
  • Series π sections weak
  • Multiple high frequency resonances
  • Virtual impedance;
  • Active damping

Fingerprint Dive into the research topics of 'Analysis and Active Damping of Multiple High Frequency Resonances in DFIG System'. Together they form a unique fingerprint.

Cite this