Projects per year
Abstract
Indirect-current-controlled active power filter (APF) is preferable compared with the direct-current-controlled APF due to its simpler structure and its direct regulation of the grid current. However, unlike direct current control, indirect current control does not have explicit current reference posing difficulty on current limiting operation. This paper proposes a current-limiting control strategy for indirect-current-controlled APF. By adding harmonic resonant controllers into the closed-loop control of the APF's output current, the harmonic components of output current can be smaller than that of the nonlinear load's current. The effectiveness of the proposed current-limiting control is verified by experiments.
Original language | English |
---|---|
Journal | I E E E Transactions on Power Delivery |
Volume | 39 |
Issue number | 6 |
Pages (from-to) | 3551-3554 |
Number of pages | 4 |
ISSN | 0885-8977 |
DOIs | |
Publication status | Published - 24 Oct 2024 |
Keywords
- Active power filter
- current limiter
- indirect current control
Fingerprint
Dive into the research topics of 'Current-Limiting Control Strategy for Indirect-Current-Controlled Active Power Filter'. Together they form a unique fingerprint.Projects
- 1 Active
-
CLEAN-Power: Compatibility and Low electromagnetic Emission Advancements for Next generation Power electronic systems
Davari, P. (PI), Xue, P. (Project Participant), Tang, Z. (Project Participant) & Frøstrup, S. (Project Coordinator)
Independent Research Fund Denmark
01/07/2022 → 30/06/2026
Project: Research