Skip to main navigation Skip to search Skip to main content

Diagnosis method of an open-switch fault for a grid-connected T-type three-level inverter system

Research output: Contribution to book/anthology/report/conference proceeding › Article in proceeding › Research › peer-review

Abstract

This paper proposes a diagnosis method of an open-switch fault and fault-tolerant control algorithm for a grid-connected T-type three-level inverter. The location of the faulty switch is identified by using the changes of average phase current and the neutral-point voltage. The fault-tolerant control algorithm can be used when the open switch fault occurs in the middle switches. It is achieved by simply modifying the conventional SVM method. The proposed methods are advantageous as they do not require additional sensors and they do not involve complex calculations. Therefore, this method is cost-effective and industrial interesting. The simulation results confirm the feasibility and effectiveness of the proposed fault-diagnosis and tolerant methods.
Original languageEnglish
Title of host publicationProceedings of the 3rd International Symposium on Power Electronics for Distributed Generation Systems
PublisherIEEE Press
Publication date2012
Pages470-475
ISBN (Print)978-1-4673-2021-4
ISBN (Electronic)978-1-4673-2022-1
DOIs
Publication statusPublished - 2012
Event3rd International Symposium on Power Electronics for Distributed Generation Systems - Aalborg Congress & Culture Center, Aalborg, Denmark
Duration: 25 Jun 2012 → 28 Jun 2012

Conference

Conference3rd International Symposium on Power Electronics for Distributed Generation Systems
LocationAalborg Congress & Culture Center
Country/TerritoryDenmark
CityAalborg
Period25/06/2012 → 28/06/2012

Fingerprint

Dive into the research topics of 'Diagnosis method of an open-switch fault for a grid-connected T-type three-level inverter system'. Together they form a unique fingerprint.

Cite this