Abstract
In grid-forming control, the swing equation of a synchronous machine is emulated by a power controller. Thereby, frequency droop, power-oscillation damping, and/or virtual inertia can be obtained. In this letter, it is shown that a phase-locked loop - which is normally grid following - can be designed so as to, in turn, emulate a generic power controller, thus, becoming grid-forming.
Original language | English |
---|---|
Journal | IEEE Transactions on Power Electronics |
Volume | 37 |
Issue number | 2 |
Pages (from-to) | 1201-1204 |
Number of pages | 4 |
ISSN | 0885-8993 |
DOIs | |
Publication status | Published - 1 Feb 2022 |
Bibliographical note
Publisher Copyright:IEEE
Keywords
- Automatic voltage control
- Couplings
- Damping
- Emulation
- Grid-connected converters
- grid-forming control
- Phase locked loops
- phase-locked loops
- Resistance
- Transient analysis
- voltage-source converters