Impedance Modeling and Stability Analysis of Grid-Connected DFIG-based Wind Farm with a VSC-HVDC

Kun Sun, Wei Yao, Jiakun Fang, Xiaomeng Ai, Jinyu Wen, Shijie Cheng

Research output: Contribution to journalJournal articleResearchpeer-review

159 Citations (Scopus)
714 Downloads (Pure)

Abstract

A new type of subsynchronous oscillation (SSO) has been observed recently in double-fed induction generator (DFIG)-based wind farm integrated via voltage source converter-based HVdc (VSC-HVdc) system. However, the mechanism of this emerging oscillation is not entirely understood. In this paper, the impedance models of DFIG with and without considering the phase-locked loop (PLL) dynamics are both derived. Then, the impedance-based simplified equivalent circuit of the multiple DFIGs interfaced with VSC-HVdc system is established. This model can be further represented as the RLC series resonance circuit to quantify the start-oscillating condition intuitively. The theoretical analysis results show that DFIGs behave as an inductance in series with a negative resistance at the resonance point, whose interaction with wind farm side VSC (WFVSC) (regard as a resistance-capacitance) constitutes an equivalent RLC resonance circuit with negative resistance. Therefore, the oscillation tends to occur due to the negative damping. In addition, the impact of various factors including number of grid-connected DFIG-wind turbines (WTs), wind speed, and parameters of PI controllers and PLL on the SSO characteristics is analyzed based on the proposed simplified model. Finally, the correctness of the theoretical analysis is validated by both the time-domain simulation and hardware-in-loop experiments.

Original languageEnglish
Article number8653346
JournalIEEE Journal of Emerging and Selected Topics in Power Electronics
Volume8
Issue number2
Pages (from-to)1375-1390
Number of pages16
ISSN2168-6777
DOIs
Publication statusPublished - Jun 2020

Keywords

  • DFIG
  • VSC-HVDC
  • Subsynchronous oscillation
  • Impedance-based method
  • Phase locked loop
  • Wind farm
  • wind farm
  • impedance-based method
  • subsynchronous oscillation (SSO)
  • voltage source converter (VSC)-HVdc
  • Double-fed induction generator (DFIG)
  • phase-locked loop (PLL)

Fingerprint

Dive into the research topics of 'Impedance Modeling and Stability Analysis of Grid-Connected DFIG-based Wind Farm with a VSC-HVDC'. Together they form a unique fingerprint.

Cite this