This paper presents a fast fault detection scheme for a hybrid line in a multi-terminal (MT) voltage source converter (VSC) high voltage DC (HVDC) system. The proposed method is based on the primary and secondary protection scheme. The discrete wavelet transforms (DWT) with Teager energy operator (TEO) and voltage polarity comparison are applied to detect the faulted line for primary and secondary protection schemes, respectively. The main and backup protection schemes are based on non-pilot and pilot methods, respectively. The proposed main and backup methods are robust against high impedance faults (HIFs). The proposed protection scheme is verified under different fault points applied on an MT-HVDC test system. The case study is performed using PSCAD/EMTDC software. Simulation results show the effectiveness of the proposed protection method for the VSC HVDC transmission line.
Original languageEnglish
Title of host publication2023 25th European Conference on Power Electronics and Applications, EPE 2023 ECCE Europe
Number of pages6
Publication date8 Sept 2023
Pages1-6
Article number10264630
ISBN (Electronic)9789075815412
DOIs
Publication statusPublished - 8 Sept 2023
Event2023 25th European Conference on Power Electronics and Applications (EPE'23 ECCE Europe) - Aalborg, Denmark
Duration: 4 Sept 20238 Sept 2023

Conference

Conference2023 25th European Conference on Power Electronics and Applications (EPE'23 ECCE Europe)
Country/TerritoryDenmark
CityAalborg
Period04/09/202308/09/2023

Keywords

  • DWT-TEO»
  • Fast fault detection
  • Hybrid line
  • Polarity comparison
  • VSC MT-HVDC

Fingerprint

Dive into the research topics of 'Protection of Multi-Terminal VSC HVDC Hybrid Transmission Line'. Together they form a unique fingerprint.

Cite this