Abstract
In this paper, the power quality (PQ) improvement of Multi-Area Microgrid (MAMGs) is addressed. To this aim, mitigation of voltage harmonics and unbalance is considered by using Distributed Generators (DGs) and Active Power Filters (APFs) in a proper way. As a novel approach, the main goal of the proposed method is to pick out redundant APFs and/or significantly reduce of DGs and APFs compensation workload by making collaboration between areas toward integrated PQ improvement of MAMG. To achieve the desired PQ indices of different areas, supervisory control is planned for proper utilization of available compensators in time. By supervisory control, harmonic propagation between areas and the system unbalance are dealt with and systemic PQ improvement of MAMG is provided. To this aim, scheduling framework is used to track PQ situation of each area. Evaluation of the proposed control scheme is carried out by a comprehensive simulation study.
Original language | English |
---|---|
Article number | 8340771 |
Journal | I E E E Systems Journal |
Volume | 13 |
Issue number | 1 |
Pages (from-to) | 864 - 874 |
Number of pages | 11 |
ISSN | 1932-8184 |
DOIs | |
Publication status | Published - Mar 2019 |
Keywords
- Active power filter (APF)
- Distributed generator (DG)
- Harmonic analysis
- Inverters
- Microgrids
- Multi-area microgrid (MAMG)
- Power quality
- Power system harmonics
- real-time power quality (PQ) tracking
- Supervisory control
- Supervisory control (SC)
- Voltage unbalance/harmonic compensation