T1 - Robust AC Voltage Controller with Harmonic Elimination for Stand-Alone and Weak-Grid-Connected Operation
AU - Pérez-Estévez, Diego
AU - Doval-Gandoy, Jesús
AU - Guerrero, Josep M.
PY - 2018/9
Y1 - 2018/9
N2 - This paper presents an ac voltage controller with a high robustness to plant model variations which can operate under a wide range of loads. A robust voltage controller is required in a droop-controlled inverter which operates in island mode with other generators or is connected to a grid. In such modes of operation, the voltage source converter (VSC) can experience a large variation in the load impedance depending on the number of parallel generators or the grid impedance value. The proposal improves the transient performance by selectively minimizing the output impedance of the system at the frequencies which typically contain the largest components of the output current. Complete harmonic control is achieved due to its zero output impedance at a set of design-selected frequencies. The design process only requires, as input parameters, the LC filter values, the sampling frequency, and a set of harmonics where load-current circulation is expected.
AB - This paper presents an ac voltage controller with a high robustness to plant model variations which can operate under a wide range of loads. A robust voltage controller is required in a droop-controlled inverter which operates in island mode with other generators or is connected to a grid. In such modes of operation, the voltage source converter (VSC) can experience a large variation in the load impedance depending on the number of parallel generators or the grid impedance value. The proposal improves the transient performance by selectively minimizing the output impedance of the system at the frequencies which typically contain the largest components of the output current. Complete harmonic control is achieved due to its zero output impedance at a set of design-selected frequencies. The design process only requires, as input parameters, the LC filter values, the sampling frequency, and a set of harmonics where load-current circulation is expected.
UR - http://www.scopus.com/inward/record.url?scp=85060315732&partnerID=8YFLogxK
U2 - 10.1109/ECCE.2018.8558074
DO - 10.1109/ECCE.2018.8558074
M3 - Article in proceeding
AN - SCOPUS:85060315732
SN - 978-1-4799-7313-2
T3 - IEEE Energy Conversion Congress and Exposition
SP - 4876
EP - 4883
BT - Proceedings of the 2018 IEEE Energy Conversion Congress and Exposition, ECCE 2018
PB - IEEE Press
T2 - 10th Annual IEEE Energy Conversion Congress and Exposition, ECCE 2018
Y2 - 23 September 2018 through 27 September 2018
ER -