Velocity Distribution in a Room Ventilated by Displacement Ventilation and Wall-Mounted Air Terminal Devices

Research output: Contribution to journalJournal articleResearchpeer-review

52 Citations (Scopus)

Abstract

The article describes experiments with wall-mounted air terminal devices. The airflow from an air terminal device influences the occupants' thermal comfort and, therefore, it is important to develop an expression for this flow in the occupied zone. The velocity at the floor is influenced by the flow rate to the room, the temperature difference and the type of diffuser. The flow is stratified at Archimedes numbers larger than four. The article gives expressions for the velocity distribution close to the floor. It is shown that openings between obstacles placed directly on the floor generate a flow similar to the air movement in front of a diffuser, and expressions for the velocity distribution in that situation are also given in the article.
Original languageEnglish
JournalEnergy and Buildings
Volume31
Issue number3
Pages (from-to)179-187
Number of pages8
ISSN0378-7788
DOIs
Publication statusPublished - 2000

Keywords

  • Displacement Ventilation
  • Air Terminal Device
  • Velocity Distribution
  • Stratified Flow

Fingerprint Dive into the research topics of 'Velocity Distribution in a Room Ventilated by Displacement Ventilation and Wall-Mounted Air Terminal Devices'. Together they form a unique fingerprint.