Wind Turbine Control Impact on Stability of Wind Farms Based on Real-Life Systems Analysis

Publication: Research - peer-reviewArticle in proceeding

Documents

  • Paper

    2 MB, PDF-document

    22/05/12

View graph of relations

This paper presents stability analysis of wind farms in frequency domain. The interaction between the wind turbine control system and the wind farm structure in wind farms is deeply investigated. Two wind farms (i.e. Horns Rev II and Karnice) are taken in to consideration in the study. It is shown that wind farm components such as long HVAC cables and park transformers can introduce significant low-frequency series resonances seen form the wind turbine terminals which can affect wind turbine control system operation and overall wind farm stability. The same wind turbine converter control strategy is evaluated in two different wind farms. It is emphasized that the grid-side converter controller should be characterized by sufficient harmonic/noise rejection and adjusted depending on wind farms to which it is connected. Various stability indices such as gain margin, vector gain margin, and phase margin are used in order to emphasize differences between the two wind farms.
Original languageEnglish
TitleProceedings of the EWEA 2012 - Europe's Primier Wind Energy Event
Number of pages8
Publication date2012
StatePublished

Conference

ConferenceEWEA 2012
LandDenmark
ByCopenhagen
Periode16/04/1219/04/12

Keywords

  • Offshore wind farms, Stability analysis, Stability margins, Wind farm aggregation, Wind turbine control