Underfrequency Load Shedding for an Islanded Distribution System With Distributed Generators

Research output: Contribution to journalJournal articleResearchpeer-review

117 Citations (Scopus)
546 Downloads (Pure)

Abstract

Significant penetration of distributed generation in many distribution systems has opened an option of operating distribution systems in island mode for economical and technical reasons. However, balancing frequency of the islanded system is still an issue to be solved, especially when the demand exceeds the generation in the power island. This paper presents a strategy to shed an optimal number of loads in the island to stabilize the frequency. The load shedding strategy is based on frequency information, rate of change of frequency, customers' willingness to pay, and loads histories. Different scenarios have been simulated with results showing that the proposed method is effective in shedding the optimal number of loads while stabilizing frequency.
Original languageEnglish
JournalIEEE Transactions on Power Delivery
Volume25
Issue number2
Pages (from-to)911-918
Number of pages8
ISSN0885-8977
DOIs
Publication statusPublished - 2010

Bibliographical note

INSPEC Accession Number: 11204421

Keywords

  • Distributed generation (DG)
  • Islanding
  • Rate of change of frequency
  • Underfrequency load shedding
  • Willingness to pay (WTP)

Fingerprint

Dive into the research topics of 'Underfrequency Load Shedding for an Islanded Distribution System With Distributed Generators'. Together they form a unique fingerprint.

Cite this