Analysis of a commercial wind farm in Taiwan: Part II: Different current-limit reactors and load tap changers on system performance

Li Wang, Tai-Her Yeh, Wei-Jen Lee, Zhe Chen

Publikation: Bidrag til tidsskriftTidsskriftartikelForskningpeer review

13 Citationer (Scopus)

Abstract

This paper presents the effects of installing variable current-limit reactors (CLRs) and adjusting load tap changers (LTCs) on the performance of a commercial wind farm in Taiwan using computer simulations. The companion paper (Part I) demonstrates the field-measured results, simulation model, and simulation results of the studied Jang-Bin wind farm with 23 2-MW doubly fed induction generator-type wind turbine generators connected to the utility system through a 23/161-kV 60-MVA step-up main transformer (MT) from six feeders. Six CLRs, which were originally designed to limit short-circuit currents under faulted conditions, are connected in series with the six feeders. The LTCs of the MT are used to adjust/regulate the secondary-side voltage at the 23-kV bus. Some simulated steady-state and transient results of the studied wind farm with variable values of the proposed CLRs and LTCs are analyzed and compared.