Abstract
This paper proposes an automatic tuning of the superheat control in a refrigeration system using a relay method. By means of a simple evaporator model that captures the important dynamics and non-linearities of the superheat a gain-scheduling that compensates for the variation of the process gain can be obtained from tuning in only one operation point. The proposed method is validated by experimental results.