A communication-less overcurrent protection for distribution system with distributed generation integrated

C. Liu, Zhe Chen, Zhen Liu

Research output: Contribution to book/anthology/report/conference proceedingArticle in proceedingResearchpeer-review

26 Citations (Scopus)

Abstract

The increasing penetration of distributed generation (DG) in distribution systems has resulted in a challenge for the conventional protection methods, due to the bi-directional power flow and the variation of fault current contribution. Moreover, the operation of distribution system in islanded mode is still an issue due to the difference between the short circuit current in islanded mode and grid-connected mode. This paper proposed a novel adaptive protection method, measuring only the local information rather than using the communication, to adapt the protection settings to the states, such as the change of operation mode (grid-connected or islanded), the change of network topology (radial or meshed) as well as the disconnection of some DG. The directional overcurrent relays (DOCR) is adopted in the distributed system to shorten the tripping time in order to maintain the DG's connection. The relay settings are calculated offline and modified online according to the state detection, including the islanding detection, the power flow detection and the fault section detection. This protection method is verified by simulating a distribution system of Denmark in DIgSILENT PowerFactory.
Original languageEnglish
Title of host publicationProceedings - 2012 3rd IEEE International Symposium on Power Electronics for Distributed Generation Systems, PEDG 2012
Number of pages8
PublisherIEEE
Publication date2012
Pages140-147
ISBN (Print)978-1-4673-2021-4
ISBN (Electronic)978-1-4673-2022-1
DOIs
Publication statusPublished - 2012
EventPower Electronics for Distributed Generation Systems (PEDG), 2012 3rd IEEE International Symposium on - Aalborg, Denmark
Duration: 25 Jun 201228 Jun 2012
Conference number: 3rd IEEE International Symposium on

Conference

ConferencePower Electronics for Distributed Generation Systems (PEDG), 2012 3rd IEEE International Symposium on
Number3rd IEEE International Symposium on
Country/TerritoryDenmark
CityAalborg
Period25/06/201228/06/2012

Fingerprint

Dive into the research topics of 'A communication-less overcurrent protection for distribution system with distributed generation integrated'. Together they form a unique fingerprint.

Cite this