Abstract
This paper develops a complete control scheme for the Modular Multilevel Converter (MMC) in a STATCOM application. The focus is laid on the internal balancing of the converter and its reliable operation under internal mismatches as well as under external unbalanced conditions. The leg energy controller ensures that the sum of the capacitor voltages of each phase are equal. An intuitive arm energy controller is also implemented which allows the decoupled control of the energy levels of every arm. The control performance of the STATCOM was evaluated under asymmetrical grid faults and the simulation results verified the capability to provide maximum reactive power to the AC grid while maintaining internal balance through the individual control of each arm energy level.
Original language | English |
---|---|
Title of host publication | Proceedings of The 42nd Annual Conference of IEEE Industrial Electronics Society, IECON 2016 |
Number of pages | 6 |
Publisher | IEEE Press |
Publication date | Oct 2016 |
Pages | 6494 - 6499 |
ISBN (Electronic) | 978-1-5090-3474-1 |
DOIs | |
Publication status | Published - Oct 2016 |
Event | 42nd Conference of the Industrial Electronics Society, IECON 2016: 42nd Annual Conference of the IEEE Industrial Electronics Society - Palazzo dei Congressi, Florence, Italy Duration: 24 Oct 2016 → 27 Oct 2016 http://www.iecon2016.org/?jjj=1471434927195 http://www.iecon2016.org/ |
Conference
Conference | 42nd Conference of the Industrial Electronics Society, IECON 2016 |
---|---|
Location | Palazzo dei Congressi |
Country/Territory | Italy |
City | Florence |
Period | 24/10/2016 → 27/10/2016 |
Sponsor | IEEE Industrial Electronics Society (IES), Institute of Electrical and Electronics Engineers (IEEE) |
Internet address |
Keywords
- Arm energy balance
- Circulating current controller
- Grid asymmetries
- Modular multilevel converter
- STATCOM