Abstract
In this paper we present comparison of different line and cable series impedance calculation methods, where the correction of a discovered PSCAD/EMIDC v.3.0.8 calculation error of the cable series impedance results n deviation under 0.1% instead of the previous method which gave approximately 10% deviation to other methods. The correction is done by adjusting he earth return path impedance for the cable model, and will thereby form the basis for a future comparison with measured data from a real full scale earth fault experiment on a mixed line and cable network.
Original language | English |
---|---|
Title of host publication | Proceedings of MEPS'02, Polish Academy of Sciences, Poland, 2002 |
Publisher | <Forlag uden navn> |
Publication date | 2002 |
Pages | 145-150 |
ISBN (Print) | 8387299936 |
Publication status | Published - 2002 |
Event | Error Correction of EMTDC Line and Cable Series Impedance Calculations Compared to Traditional Methods - Duration: 19 May 2010 → … |
Conference
Conference | Error Correction of EMTDC Line and Cable Series Impedance Calculations Compared to Traditional Methods |
---|---|
Period | 19/05/2010 → … |
Keywords
- Cable model
- Series impedance
- Skin-effect
- Earth return path
- PSCAD/EMTDC